Electrical Maintenance Services for Apartments in Bangalore

Reshma Facilities Management maintains the electrical systems of apartments and gated communities in Bangalore: common lighting, panels, DG sets, transformers and fire alarm systems. Our electricians work to a preventive schedule and keep the records the building needs for inspections.

What’s covered

System
Work done

Common lighting

Corridors, staircases, basements, street and landscape lights

Distribution boards and panels

Tightness checks, thermal checks, breaker testing

Earthing

Annual resistance measurement, pit maintenance

DG sets

Weekly test run, fuel, coolant, battery, auto changeover (AMF)

Transformer and HT panel

Oil level, breather, oil testing, thermography

Pump room electrics

Starters, level controllers, motor protection

Fire alarm system

Panel, detectors, hooters, manual call points

Firefighting pumps

Main, jockey and diesel pumps, hydrant pressure

Energy metering

Common area meter readings and consumption tracking

DG set maintenance

A DG set that has not run under load for weeks may not start when the power goes. We test run it weekly, check fuel, coolant and battery, and confirm the automatic changeover works. Major servicing is coordinated with the DG manufacturer’s service partner.

Transformer maintenance

Apartment transformers usually fail for reasons that were measurable months earlier. Oil absorbs moisture and loses its insulating strength. The silica gel breather turns pink and nobody replaces it. A loose termination heats up where thermography would have caught it.

Check

Frequency

Oil level, temperature, breather

Monthly

Oil dielectric (BDV) test

Periodic

Thermography on HT and LT panels

Periodic

Earthing resistance

Annual

HT panel relay and protection check

To schedule

 

A failed transformer costs lakhs to replace and leaves the building on DG power while it is fixed.

Fire alarm AMC

A fire alarm panel can show a healthy board while a zone has been isolated for months. Technicians isolate zones to silence false alarms and forget to restore them. Detectors get painted over during repaints. Hooters get disconnected after complaints.

We test zone by zone and report which devices actually responded, not just that the panel shows green.

Item

Frequency

Panel health and fault log

Monthly

Detector testing by zone

To schedule, logged per device

Hooters and manual call points

Monthly

Fire pumps and jockey pump

Weekly test run

Hydrant pressure and hose boxes

Monthly

Extinguisher pressure and refill dates

Monthly register

 

Cost

Resident electricians are priced monthly as part of the facility contract. Transformer testing, thermography and fire alarm AMC can be taken separately.

Frequently asked questions

A weekly test run on load is standard practice for apartments, along with a monthly check of fuel, coolant and batteries.

Periodically, as recommended by the manufacturer and the electrical inspectorate. Oil condition is also checked visually every month.

Yes, on request, billed to the resident separately.

Scroll to Top